Branch circuit sizing playbook
Goal
Select a branch circuit that meets load needs, conductor limits, and protective device requirements with a clear inspection trail.
Inputs you must know before you start
- Load type and continuous or non-continuous classification.
- Voltage, phase, and environment (ambient, bundling, insulation type).
- Installation method (raceway, cable, exposed run).
- Equipment instructions that affect terminals or conductor size.
The path (in order)
- Classify the load and determine the design current.
- Select conductors based on ampacity after adjustments.
- Choose the OCPD from standard ratings that fit the conductors.
- Confirm grounding and bonding paths are complete and compatible.
- Document assumptions and NEC references used.
This is
A practical sequence for sizing a standard branch circuit that ties conductor selection to OCPD choice and grounding continuity.
This is not
A complete design for specialty equipment or systems with dedicated articles.
Inspection-ready checklist
- Load calculation and classification documented.
- Conductor ampacity after derating recorded.
- OCPD rating matches conductor limits and standard sizes.
- Terminations and equipment instructions verified.
- Grounding and bonding path verified.
Worked example
A 20A continuous load at 120V requires a branch circuit sized above the design current. Choose a conductor that supports the adjusted ampacity, then pick the nearest standard OCPD rating that stays within conductor limits.
Cross references
- Primary: 210
- Secondary: 110, 300, 310, 240, 250